CABLE CONSTRUCTION
Conductor:
1.5mm2 solid Bare Copper
Nom.Dia:0.0543±0.0003″(1/1.38±0.008mm)
Insulation:
Type.silicone rubber
Dia over Insulation:0.1114±0.0040″ nom.(2.8±0.1mm)
Drain Wire:1/1.38±0.008mm solid Tinned-Copper
Shield:0.0047″(0.120mm)thick Fireproof aluminum foil
ELECTRICAL PROPERTIES:
- Temperature Rating:-40℃~+90℃
- Operating Voltage:300 /500V
- Withstand voltage test :
- Between insulated conductors,AC: 2000V / 5min, no breakdown
- Between insulated conductor and ground wire,AC: 1000V / 5min, no breakdown
- Maximum resistance:12.1 0hms/KM at 20℃
STANDARD:
- All these cables comply to:
- Application of insulation :EN50363-1、EN50363-2-1、BS2683
- Inner Conductor Diameter:BS EN 60228
- Insulation:EN50363-1、EN50363-2-1、BS2683
- Sheath :EN7655-6.1、BS EN50267-2-1BS60754、BS2683
- Smoke emission:EN 61034-2: 2005+A2:2020
- Corrosive and acid gas:EN 60754-1: 2014
- Flame propagation on a single cable:EN 60332-1-2:2004
- Fire resistance(single cable) :BS6387、BS EN50200、BS 8434-2
- Fire resistance time:PH30-PH120